HEALTHCARE CASE STUDY
Commercial Healthcare Facility Water Mitigation & Surgical Suite Recovery
SITE: SURGICAL SUITE 2B MONITOR: -0.032 IN-WC Commercial Healthcare Facility Water Mitigation & Surgical Suite Recovery SITE BASELINE Commercial Medical Complex 14,200 sq. ft. outpatient surgical clinic. Pressurized Category 3 hydronic HVAC loop failure. Initial psychrometrics: 78.4°F / 88.6% RH / 132 GPP . Wall framing registered 34.2% WME with imminent risk of cross-contamination into clean surgical theaters. Constructed airtight poly containment with zipper airlocks maintaining -0.032 in-WC negative pressure differential. Deployed six 2,000 CFM HEPA air filtration units generating 8.2 ACH . Mobilized 5,000 CFM desiccant unit delivering < 34 GPP deep-cavity vapor removal with EPA botanical sanitization. Spore trap sampling confirmed indoor levels dropped from 8,460 outdoor baseline to 340 spores/m³ . Zero marker pathogens detected on culture plates. Post-Remediation Verification (PRV) Clearance Certificate issued within 6 days . EVIDENCE DOSSIER • RESTORATION STAGING Trailer-mounted desiccant equipment and LGR drying units deployed to establish closed-loop equilibrium drying.